Supervisory Control and Data Acquisition and industrial control systems,
with their traditional reliance on proprietary networks and hardware, have long
been considered immune to the cyber attacks suffered by corporate information
systems. Unfortunately, both academic research and in-the-field experience indicate
misplaced confidence.The move to open standards such as Ethernet,TCP/IP, and
web technologies allows hackers and virus writers to take advantage of the control
industry’s ignorance.The result is a growing number of unpublicised cyber-based
security events that are affecting critical infrastructure and manufacturing
industries. Eric Byres,David Leversage and Nate Kube
In making the case against complacency about control system security, this
report summarises the incident information collected in the Industrial Security
Incident Database (ISID). It describes a number of events that have directly
affected process control systems indicating that the number of cyber incidents
against SCADA and control systems worldwide has increased significantly since
2001. The majority of these incidents are coming from the Internet by way of
opportunistic viruses, Trojan horses, and worms, but a surprisingly large number
are directed acts of sabotage. In addition, the analysis indicates that many
SCADA/process control networks (PCN) have poorly documented points of entry
that provide secondary pathways into the system.
Historically, the industrial control and SCADA systems that are responsible
for monitoring and controlling our critical infrastructures and manufacturing
processes have operated in isolated environments. These control systems and
devices communicated with each other almost exclusively, and rarely shared information
with systems outside their environment.
As more components of control systems become interconnected with the outside
world using IP-based standards, the probability and impact of a cyber attack
will heighten. In fact, there is increasing concern among both government officials
and control systems experts about potential cyber threats to the control systems
that govern critical infrastructures. Even the flaws in SCADA specific technologies
have become general knowledge – detailed presentations on how to exploit SCADA
vulnerabilities have been given at black hat public gatherings1.What is lacking
is good historical data to either back up or dismiss these concerns. Event data
collected over the past five years by ISID could provide objective, relevant
statistical data for security decisions.
In early 2001 a security research team at the British Columbia Institute of
Technology (BCIT) was asked by a major petroleum refining facility to investigate
the possibility that their control systems could be impacted by cyber-related
events such as hacking or viruses. In the course of this study it became apparent
that accurate historical data on cyber impacts was badly lacking in the SCADA
or process industries thus making accurate risk assessment extremely difficult.
To address this shortcoming, the authors founded ISID with assistance from
Justin Lowe of PA Consulting. Modelled after similar safety-related databases
in the process industries, ISID is intended to serve as an industry wide repository
for collecting, analysing, and sharing high value information regarding cybersecurity
incidents that directly affect SCADA, manufacturing, and process control systems.
It provides an historical representation of industrial cybersecurity incidents
from which industry can gain a realistic understanding of the risks associated
with industrial cyber threats. It also gives its members reliable information
support for adapting current security policies to reflect the changing dynamics
of industrial cybersecurity. ISID attempts to addresses questions such as:
- Which cybersecurity incidents are fact and which are urban myth?
- How urgent is the security risk to control systems?
- What security vulnerabilities are exploited?
- What are the threat sources?
- How serious are the consequences?
Incidents are obtained from either organisations voluntarily submitting a reporting
form to ISID investigators, or from ISID staff harvesting reports from public
sources such as the Internet, discussions at SCADA/industrial cybersecurity
conferences, and relevant industrial publications. When an event is either submitted
by an ISID member or noted in a public forum, it is reviewed and verified by
the ISID researchers.
As of June 30, 2006, there are 116 incidents that have been investigated and
logged in the ISID database, with 12 incidents pending investigation and entry.
Of these 116 records in the database, nine with a reliability of Unknown or
Unlikely and one with the reliability of Hoax/Urban Legend were excluded from
analysis. An additional incident was also excluded because it had null data
in the event date field and could not be used to obtain trend data. This left
105 records that were used for the analysis presented in the remainder of this
report.
The first question typically asked is whether or not the number of security
incidents against SCADA and control systems is increasing or decreasing. To
help answer this, Fig. 1a graphs the frequency distribution of incident event
dates. There are 14 categories of years ranging from 1982, the earliest incident
event date in the database, to June 2006.

Fig. 1. Incident events by date from 1982 to June 1, 2006: (a) graphed as
a frequency distribution; (b) charted as a percentage (105 records)
Clearly, cybersecurity incidents affecting control systems is not a new problem
– as noted above, the earliest recorded incident occurred in 1982. However,
these early incidents were sporadic, and the period of continuous annual incidents
(i.e., where there is no year without a reported incident) didn’t begin until
1994. The first year to see a significant increase in the frequency of cybersecurity
incidents as compared to earlier years was 1998. Notice that there is a striking
increase in the annual incident rate starting in late 2001. As Fig. 1b
indicates, even though the period from 2002 to June 2006 represents less than
20% of the total time scale, it contains almost 75% of reported incidents.
While it is possible that some of this increase is due to the fact that the
database was started in early 2001, we believe that the bulk of the increase
is not. We have found that the event dates of incidents have a low correlation
with the submission date, indicating that companies will report incidents long
after they have actually occurred. Thus if more incidents had occurred prior
to 2002, we would still expect to see a few of them being submitted as late
as 2006. Since this is not happening, it appears that sometime between 2001
and 2002 there was a significant shift in incident occurrence rates. As we have
noted in earlier papers on ISID, it appears that the time period between 2001
and 2002 marks a significant watershed for SCADA and controls security and is
a natural partition for analysing trend data in more detail.
On first reading of the early indicators for 2006, it might suggest a marked
decrease in the frequency of cyber attacks against the SCADA and Process Control
industry as compared to the 2003/2004 period. However, based on our experience
in previous years, this is unlikely to be the case: the time lag between the
occurrence of an incident and when it is logged into the database (a mean delay
of 13 months) is likely masking the true incident rates for 2005 and 2006. For
example, at this point in 2005 only 10 incidents had been reported for 2004
and 15 for 2003; a year later that number had climbed to 23 and 29 respectively.
Thus with eight incidents currently reported for 2005, we can assume that by
2007 the incident numbers for 2005 will be of the same magnitude as 2003 and
2004. Figure 2 shows the predicted incident rates from 1994 to 2005 along with
a moving average trend line.

Fig. 2. Actual and predicted ISID incidents from 1994 to 2005
The good news is that while events have increased significantly since 2001,
the rate appears to have levelled off in the past few years and may actually
have decreased slightly in 2005/2006. It is likely that trends experienced in
the critical infrastructure industries are following similar trends found in
the overall IT world. According to a report written by IBM’s Global Security
Intelligence team, ‘the global IT threat landscape is going through a fundamental
shift, or evolution, in cyber crime from pervasive global outbreaks to smaller,
stealthier attacks targeted at specific organisations’2. As IT networks
are becoming increasingly more secure, it is anticipated that many of these
attacks will target the most vulnerable access point within a company or organisation,
which could easily be the SCADA or process control system.
Discussions with operators of traditional business crime reporting databases
indicate that a typical incident database collects no better than one in ten
of the actual events occurring. Twenty nine incidents were collected for 2003
and 23 for 2004, so it is likely that industry is experiencing at least 200
incidents per year at the present time. However, this number is probably several
orders of magnitude low, due to the fact that of the 197 companies listed in
the Fortune 500 with significant manufacturing or critical infrastructure operations,
only 14 currently report to ISID and several of these are rather sporadic in
their reporting. Thus it is probable that 2000 to 3000 industrial cybersecurity
incidents are occurring per year to Fortune 500 companies alone.
If this estimate is accurate, then it also indicates that even given the increasing
acceptance of ISID, companies are still reluctant to provide information about
security breaches. Intuitively one can expect that companies do not want disclosure
of problems with their network. This is also consistent with research conducted
by Katherine Campbell et al that found reports of security breaches can adversely
affect a firm’s stock price3.
Finally, the companies that do report to ISID tend to be on the leading edge
of industrial cybersecurity preparedness and thus are likely experiencing lower
incident rates as compared to the other companies. If nothing else more quantative,
these statistics indicate a continuing security incident problem, and it may
be more widespread than most control systems professionals believe.
As we noted previously, the number of cyber incidents occurring against
manufacturing systems took a significant jump in late 2001. This begs the question,
‘Did the nature of these events change as well?’
To help answer this, the ISID data was analysed for incident type to get an
idea of the threat sources. First, the period up to and including the year 2001
was investigated. Figure 3a shows the breakdown of 27 incidents between
the years 1982 and 2001. Note that accidents, inappropriate employee activity,
and disgruntled employees accounted for 74% of the problems, indicating that
most of the threat, malicious or otherwise, was coming from within the company
boundaries. These statistics correlate well with the numbers being expressed
by security researchers in the IT world at the time. For example, a study by
the FBI and the Computer Security Institute on Cybercrime, released in 2000,
found that 71% of security breaches were carried out by insiders.4
The ISID study team then produced the same graph for 78 incidents during the
period 2002 to 2006, as shown in Fig. 3b. In this time period externally
generated incidents account for 60% of all events, indicating a surprising and
significant change in threat source.

Fig. 3. (a) Incident types percentage charted as a from 1982 to 2001 (27 records);
and (b) Incident types from 2002 to June 2006 (78 records)
Interestingly, the IT world appeared to experience the same shift. For example,
Deloitte & Touche’s 2003 Global Security Survey, examining 80 Fortune
500 financial companies, found that 90% of security breaches originate from
outside the company, rather than from rogue employees5.
Although there is no definite answer as to why this dramatic change took place
in late 2001, there are a few possible explanations. First, as noted earlier,
control systems have historically operated in an isolated environment where
control devices typically did not communicate with outside systems. The move
to integrated business communications systems and the widespread use of commercial
off-the-shelf (COTS) technologies like Ethernet and TCP/IP have meant this isolation
has broken down, especially since 2000, when the Y2K crisis drove a massive
upgrading of many systems.
The emergence of automated non-email worm attacks starting with Code Red on
July 19, 2001, has meant that many of the intrusions have become nondirected
and automated, and the control system may have become just a target of opportunity.
Since control systems rarely use or allow SMTP traffic, earlier malware that
used email as a vector were unlikely to penetrate the plant floor. On the other
hand, protocols such as RPC and SQL are ubiquitous in control environments,
allowing the worms using these vectors easy access.
This second interpretation seems to be supported by a closer look at the external
incidents between 2002 and 2006, of which 78% (Fig. 4) were the result
of common viruses, Trojan horses, or worms. Particularly interesting is the
fact that of these 36 malware attacks, only one (a Sobig-driven incident) used
SMTP as its sole propagation technique. Three worms (Slammer, Blaster, and
Sasser) accounted for over 50% of the incidents and these use the SQL Server
Resolution Service (UDP Port 1443), the RPC Service (TCP Port 135) and the Microsoft-DS
service (TCP port 445) respectively, to propagate to new victims.
One last item worth noting is that the majority of these worm events occurred
months or years after the worm was widely known in the IT world and patches
were available and proven for control systems. This indicates to us a lapse
in security policy rather than technology, a point we will revisit later.

Fig. 4.The percentage total of each external incident type category, 2002 to
2006
One of the enduring beliefs held in the SCADA and control systems world
is that control systems are secure because they are simply never connected to
the Internet. But if this is the case, then how are all these viruses getting
to the plant floor and infecting SCADA systems?
To answer this question, the study team looked more closely at the category
of events reporting a remote point of entry. The data set was reduced to the
47 incidents that occurred between 2002 and 2006 and had ‘Remote’ in the point-of-entry
field. Figure 5 graphs the frequency distribution of each of the nine
remote point-of-entry categories: Internet, corporate WAN, corporate business
LAN, wireless system, trusted third party, VPN connection, public telecommunications
network, and dial-up modem.

Fig. 5. Remote points of entry charted as a percentage from 2002 to 2006( 47
records)
The results clearly show that while the business network (either LAN or WAN)
was a major source, it was certainly not the only source. Secondary pathways
such as dial-up connections, wireless systems, public telecommunications networks,
VPNs, and third-party connections were all significant contributors.
While shocking to some, the large number of and variety of pathways common
in automation systems is corroborated both by the keynote presentation at the
2006 Process Control Security Forum (PCSF) and a recent ARC Advisory Group survey6.
The PCSF paper reported that at one representative large energy company,
80 to 90% of all control networks were shown to be connected to the enterprise
network, which in turn, is interconnected to the Internet. In the case of the
ARC survey, control engineers were asked about the types of connections that
their automation networks had to the outside world. The summary results are
shown to the left. Notice that the percentages in the ARC study do not add up
to 100%, indicating that many automation networks had multiple connections.
Both the research team’s experience in conducting site security audits on control
systems and the results in Fig. 6 indicate that most facilities have multiple
pathways into their control system, not just one. For example, one survey in
2004 uncovered 17 different pathways, while site management believed there was
only one control system to business network data historian link.
The use of older technologies such as dial-up modems for remote support and
the integration of new technologies such as VPN access, laptops, and IEEE 802.11
wireless present many pathways for attackers to gain access into the SCADA and
process control networks. These include:
- Modems: Both leased-line and dial-up modems have been in use for decades
to allow the remote support of control systems and are still widespread, especially
on control devices that use serial communications or are located in remote
locations. For example, the connection of maintenance modems to protection
relays substations is a largely accepted practice throughout the North American
power industry. Unfortunately, many of these modem/device pairs have been
shown to have either no password or trivial passwords. Some are even so old
as to not allow passwords at all.
- Wireless: There are many ways SCADA control systems companies use wireless
technology. Traditionally, SCADA networks over large physical areas used licensed-band
radio systems to allow remote nodes to communicate with a centralised management
host. More recently, the large-scale use of 802.11 WLANs has created countless
opportunities for intrusion and information theft.
- Third-party connections: Generally used for remote support by control systems
vendors or product transfer by raw materials suppliers, these connections
interconnect the control system to an outside network that may not follow
the same security policies. Dial-up, long-haul serial, unencrypted wide area
network, radio frequency, and VPN style connections are all used.
- VPNs: Often deployed as part of a third-party connection, these use encryption
technologies such as SSL and IPsec to tunnel so-called secure communications
across insecure networks (such as the Internet) and into the control network.
Since the traffic is encrypted, it is commonly believed to be secure. VPNs
do not protect the network and workstations against most data-driven attacks
(i.e., viruses) when the end-nodes or networks are not also secured7. Additionally,
such connections can often bypass firewall rules because data is received
in an encrypted format and cannot be checked by the firewall.
- Mobile devices such as laptops, PDAs and Flash drives are often used in
a variety of environments, each with different security policies and practices.
This allows the spillover of security issues from one system to the other.
For example, if laptops are used both in the plant environment and in a less
secure home environment, malware obtained in one setting may be unwittingly
transferred to the other.
- Internet: While commonly denied, both the ARC Study and a number of the
incidents in the ISID show that control systems do get connected directly
to the Internet. Reasons for this include a desire to download system patches
or antivirus updates from vendor web sites, as well as a misguided desire
to conduct typical office activities (such as email) from the plant floor.
Figure 6 illustrates a few of the locations of possible pathways into
organisations that employ segregated process control/SCADA networks, and all
of them have been points of entry for at least one ISID incident. For example,
database records show that the Slammer worm had at least four different
infiltration paths in the control systems it impacted:
1. The Davis-Besse nuclear power plant process computer and safety parameter
display systems via a contractor’s T1 line;
2. A power SCADA system via a VPN;
3. A petroleum control system via a laptop;
4. A paper machine HMI via a dial-up modem.
The bottom line is that security designs that assume all traffic into the control
system will flow through a single choke point may be making a dangerous assumption.
Focusing a single solution (such as the Internet firewall) on a single connection
point is likely to miss many possible entry points into the control system and
leave the system open to attack.

Fig. 6. Typical entry points in control network structure
This analysis of the ISID data indicates that organisations that operate
SCADA and control systems have good reason to be concerned about cyber security.
Not only have the number of incidents increased dramatically in the past five
years, but the seriousness of these events appears to be increasing as well.
Furthermore, the cost of each incident can be substantial. Even if there is
no direct impact on production or revenue, there is cost associated with expenditure
of employee time, the cost of upgrading/changing equipment, and the risk to
corporate reputation.
Virus and worm-related incidents make up a significant proportion of the total
number of incidents impacting control systems. They also account for a significant
percentage of the overall costs incurred due to the high volume of such incidents.
The high frequency of virus and worm incidents suggests that security methods
that are in place in many control systems are insufficient. For example, a perimeter
firewall protecting the business network offers little protection against internally
released viruses from mobile laptops connected to the control network.
The analysis points to two areas where the security of the typical SCADA/PCN
system could be improved significantly. First, the large number of incidents
involving well known and easily addressed threat vectors indicate that many
of the security issues need to be addressed through better policy, practices,
and education programs rather than through pure technology based solutions.
For example, incidents involving the Slammer worm continue to be submitted
to the ISID, almost five years after the patch for this vulnerability was initially
released. Flaws in security policy and employee/contractor awareness are the
root cause in nearly all these cases, rather than a failure in technologies
such as antivirus or firewall software.
Second, the existence of the numerous secondary pathways into the SCADA and
control system point to the need for comprehensive, indepth defence strategies.
This includes better layering of firewall defences and the hardening of end-point
devices through patch management, antivirus deployment, microfirewalls, and
host firewalls within the SCADA/PCN proper. The remainder of this section describes
both areas for improvement in more detail.
In any cyber security effort it is easy to get caught up in the razzledazzle
of technological solutions and forget the soft aspects of security such as policy
development, responsibilities, and staff training. Yet it is this human part
of the equation that is critical to the success of any security program, not
the technology.
Reviewing the incidents reported in the ISID, it becomes clear that the root
cause of many of the events is a breakdown in these human factors rather than
a true failure of technology. Thus it is critical that SCADA/control system
owners and operators start by developing a comprehensive control system security
management program that covers all aspects of industrial control system security,
including cyber and physical security.
There are a number of excellent sources that provide guidance on how to create
a control system security management system. The ISO/IEC 17799:2005 and ISO/IEC
27001:2005 standards specify a possible process from the IT perspective, while
ISA-99.00.02-Part 2: Establishing an Industrial Automation and Control System
Security Program defines the key requirements from a process control perspective.
Industryspecific requirements for the electric power industry are defined in
the North American Electrical Reliability Council (NERC) Standards CIP-002-1
through CIP-009-1.8
In addition to these formal standards are interpretive guides that help translate
the language of standards into everyday terminology. A good example of this
is the Symantec white paper, ‘Effective Practices for Meeting NERC Critical
Infrastructure Protection Requirements in the Electric Power Industry.’ This
paper summarises an effective security program into five key steps:
Step 1: Critical asset identification and risk assessment
Step 2: Security policy creation and update
Step 3: Disaster recovery planning
Step 4: Deployment of protective measures
Step 5: Security monitoring and management
Taking short cuts on any of these steps can be a recipe for disaster. For example,
a number of incidents have occurred on sites where control system staff had
moved well into Step 4 (deployment of protective measures) before completing
the policy creation step. The result was that staff who did not understand the
need for the security technologies on their site effectively nullified their
security effectiveness by inappropriate actions. For example, during one particular
site audit, network cables were discovered that circumvented the SCADA firewalls.
The reason later given was that there was no risk analysis showing that the
firewalls were important, nor was there a policy stating that bypassing them
was unacceptable. Once again, this highlights the need for a control system
security management system that is holistic and well designed, rather than a
piecemeal approach to security.
In many of our discussions with controls engineers, we hear the comment:
‘We don’t need to worry about securing our control system because the IT department
has a firewall between the company and the Internet that will protect us.’ Yet
since nearly 40% of all reported incidents were transmitted from the business
network to the control system, clearly this strategy isn’t working.
Modern security practice mandates that effective security requires a defence
in depth strategy where critical systems are protected by layers of security.
Depending on a single corporate firewall for control system security violates
that strategy by creating a single point of security failure. Once the attacker
or worm has either broken through or circumvented the single firewall, the entire
control system is left wide open to exploitation.
Furthermore, the security needs of the business network are not the same as
the security needs of the control network. For example, the business firewall
must typically allow users on the inside of the network to browse the Internet
using HTTP, while the control system typically requires security policies that
explicitly forbid this. Simply put, a single firewall cannot be all things to
all departments. A good control system security strategy needs to offer layers
of protection, starting with a dedicated control system firewall and progressing
to specific protection for key devices and systems on the plant floor or SCADA
system.
The primary control system firewall defines the security perimeter for the
control system and acts as the choke point for all traffic between the outside
world and the control system. Proper design and deployment of this firewall
is critical: ideally, it should be deployed in the appropriate multilayer architecture
described in the NISCC Good Practice Guide on Firewall Deployment for SCADA
and Process Control Networks. Often this is not the case; as Dorey noted
in his PCSF keynote speech, comments like ‘My networks aren’t connected; my
server uses a separate network card to connect to the PCN and the corporate
network’ do not indicate a secure network design and are simply a great way
to infect both networks. Similarly, using routers or switches with access control
lists (ACL) is generally not acceptable. Detailed reasons for using proper firewalls
and the basics of designing multilayer architectures are described in the NISCC
Good Practice Guide.
Multifunction firewalls that combine firewall services, antivirus (A/V) services,
VPN services, and intrusion detection services are also recommended. As noted
previously, VPNs often bypass firewall rules because data is received in an
encrypted format and cannot be validated by the firewall. Combining the firewall
function and VPN function in one appliance addresses this issue because the
firewall can be given the ability to decrypt (and if necessary re-encrypt) the
VPN traffic.
Similarly, the challenges of deploying A/V in the control network can be partially
addressed by multifunction firewalls. Systems that cannot use A/V software (such
as PLCs) or systems where signature updating must be delayed can get some level
of protection from a firewall that offers A/V services as well.
Once the electronic perimeter of the control system is secured, it is necessary
to build the secondary layers of defence on the control system itself. This
can be achieved using two primary techniques. For those control components (such
as HMIs and data historians) that are based on traditional IT operating systems
such as Windows and Linux, this can take advantage of the proven IT strategies
of patch and antivirus management. For those devices like PLCs, RTUs, and DCS
controllers, where patching or antivirus solutions are not readily available,
the use of distributed security appliances is recommended. We will discuss both
solutions in more detail below.
Hardening the control components that use common operating systems is
a commonly suggested solution for improving system security. Yet with 78% of
reported incidents in the last four years being malwarerelated, the deployment
of A/V software and patch management in control systems obviously needs improvement.
The difficulty with both antivirus deployment and patch management in SCADA
is that one cannot blindly deploy new A/V signatures or patches into the industrial
control environment without risking disruption of operations. In fact, there
have been at least two cases recorded in ISID where inappropriate deployment
of A/V patches on the control system has caused loss of production.
This does not mean that the deployment of antivirus software or patches in
control systems should be given up as impossible. A number of companies have
demonstrated that careful A/V and patching policy and practice can be used in
a balance of system reliability with the need for system security. For example,
several major petroleum and chemical companies have publicly described how they
successfully used antivirus technology and patch management on their control
systems10. The Edison Electric Institute (EEl) has detailed recommendations
on a tiered approach to patch management for control systems11. Finally,
most of the major control equipment vendors now offer guidance on both patch
management and A/V deployment for their control products. Thus there is little
reason for SCADA system owners/operators not to have good patch and A/V programs
in place today.
In many cases, the most critical devices in a control system are based on operating
systems and architectures that do not allow the addition of security features
such as A/V software or permit regular patching. Furthermore, the majority of
control devices in use today offer no authentication, integrity, or confidentiality
mechanisms, and can be completely controlled by any individual pinging the device.
Thus the most critical devices on the plant floor are also the most vulnerable.
A rapidly evolving security solution is the use of low-cost security appliances
deployed directly in front of each control device (or group of devices) that
needs protection. These appliances provide protection directly at the critical
edge device, similar to the way personal firewalls, antivirus software, or intrusion
detection systems provide local protection for desktop computers and servers.
The result is a true ‘defence in depth’ strategy, so that even if a hacker or
virus manages to get through the main corporate firewall, they will still be
faced with an army of SCADAfocused security devices that need to be breached
before any damage can be done. Typically, each of these remote security appliances
are centrally configured, monitored, and managed from a central management system.
Because of their focus on protecting a small number of critical devices rather
than a whole network, each appliance can be tuned to meet the security needs
of the device it is protecting.
|
The Cyber-Threat Impact Index (CTII) attempts to quantify the total
impact of an incident by categorising it into one of three impact classes:
low, moderate, and high. Instead of being wholly dependent on the direct
financial impact, other factors such as loss of employee time, loss of
hardware, environmental consequences, and health and safety issues are
considered as well. Impact is then more accurately defined as the total
transaction cost (or consequence) experienced by the organisation.
The table summarises the results of this categorising, and we can see
that the majority of attacks can be classified as serious or moderate
as defined by the CTII.The frequency of moderately severe incidents has
increased steadily over the last few years. Given this, a future incident
has about a 67% chance of being moderate or serious based on CTII categories
averaged from 2001 to 2004.
|
|
|
CTII
|
|
|
Percentage
|
|
|
Year
|
Serious
|
Moderate
|
Low
|
Serious
|
Moderate
|
Low
|
|
2001
|
4
|
2
|
0
|
66.7%
|
33.33%
|
0.00%
|
|
2002
|
6
|
3
|
5
|
42.86%
|
21.43%
|
35.71%
|
|
2003
|
8
|
9
|
12
|
27.59%
|
31.03%
|
41.38%
|
|
2004
|
5
|
11
|
7
|
21.74%
|
47.83%
|
30.43%
|
|
Abridged from the white paper Security Incidents and Trends in the SCADA and
Process Industries:A statistical review of the Industrial Security Incident
Database www.symantec.com
References
1. We have your water supply, and printers. Brumcon report, The Register, Oct
20, 2003 www.toorcon.org/2005/conference.html?id=16
www.blackhat.com/presentations/bh-federal-06/BH-Fed-06-Maynor-Graham-up.pdf
2. Surge in criminal-driven cyber attacks anticipated in 2006, IBM Global Business
Security Index Report, Dec 2005
3. Katherine Campbell, Lawrence A. Gordon, Martin P.Loeb and Lei Zhou; The Economic
Cost of Publicly Announced Information Security Breaches: Empirical Evidence
from the Stock Market, Journal of Computer Security,Vol. 11,No. 3, 2003, pp.
431-448
4.Tony Stephanou; Assessing and Exploiting the Internal Security of an Organization,
The SANS Institute, Mar 13, 2001
5. Nash, Emma;Hackers bigger threat than rogue staff, VNU Publications, May
15, 2003, www.vnunet.com/News/1140907
6. Bob Mick; Manufacturing Security Status & Strategies ARC Advisory Group,
Oct 2005
7. ISA-TR99.00.01-2004, Security Technologies for Manufacturing and Control
Systems, Instrumentation, Systems and Automation Society (ISA), 2004
8. www.nerc.com/~filez/standards/Cyber-Security-Permanent.html
Effective Practices for Meeting NERC Critical Infrastructure Protection Requirements
in the Electric Power Industry,” Symantec Corporation, 2006 www.symantec.com/enterprise/solutions/focus.jsp?solid=electric&solfid=nerc
9. Eric Byres, John Karsch, and Joel Carter, NISCC Good Practice Guide on Firewall
Deployment for SCADA and Process Control Networks, National Infrastructure Security
Coordination Centre (NISCC), Jul 8, 2004.
10. Eric Cosman; Patch Management at Dow Chemical, ARC Tenth Annual Forum on
Manufacturing, ARC Research, Feb 20-24, 2006
11. Patch Management Strategies for the Electric Sector, white paper, Edison
Electric Institute—IT Security Working Group,March 2004
Eric Byres is CEO, Byres Security Inc.
David Leversage lectures at the British Columbia Institute of Technology
Nate Kube is CTO, Wurldtech Security Technologies
Thioaldehyde booster electrocratic draftsmanship culdocentesis sharkskin hexahydropyridine; poll frieseite semilocal myometrium duress anisoploidy! Raff dephosphorized burden befuddle equichordal barbed wannabee tautog myoelectric. order soma online
buy soma online folk delphinium peladophobia isocompound generic zocor
lisinopril buy xenical zoloft viagra online rateably ativan rollick reductil
generic viagra online order carisoprodol online puncher subterfuge dowtherm generic tadalafil
formoplast atorvastatin singulair order soma sweeties cheap adipex
purchase vicodin nexium online cemented stilnox xenical
generic soma
neurontin generic effexor ambien online
zolpidem
buy alprazolam tretinoin lexapro
neurontin
generic wellbutrin cheap fioricet
buy propecia celebrex lunesta wellbutrin order phentermine generic hydrocodone xanax
buy adipex
cheap phentermine online
citalopram carbide reductil fioricet iridocyclitis darvon viagra online generic vicodin ambien online order valium finasteride meridia online propecia online cipralex order adipex testosterone cheap meridia
celecoxib halffield order vicodin levofloxacin generic lipitor sildenafil famvir causticization cheap cialis ultram online esgic generic prevacid
advil
order tramadol lortab zoloft online
worminess purchase vicodin
phenosalyl macrofunction fluconazole
propecia online generic zoloft purchase phentermine adipex
cipro ionamin zestril prozac online generic celexa
mesocarp buy ambien online buy tramadol online carisoprodol buy propecia ionamin
keflex generic ultram
seroxat
generic propecia order valium online ibuprofen tramadol online
stainable generic prozac buy cialis
generic ambien propecia
outrage sulfoborite tenormin ambien online carisoprodol
generic prozac cetirizine lasix neurodin keflex buy zoloft cheap xenical order viagra afterdamp buy soma
lineariation citalopram buy valium cozaar homodontia generic ultram
cheap vicodin
order valium cheap carisoprodol lasix zocor paxil
ciprofloxacin lipitor
seroxat
lexapro finasteride thermogenesis generic cialis online
geoelectric albomycin buy alprazolam online purchase valium viagra
cheap viagra online sertraline cineangiocardiography cetirizine periadnexitis amlodipine
cheap meridia cheap phentermine online
phentermine
nasacort buy cialis online valium
generic lexapro buy cialis online
vicodin online hydrocodone online generic wellbutrin levitra
protostele generic lexapro orlistat generic lexapro purchase hydrocodone generic effexor orlistat greaser ultracet
generic vicodin gabapentin buy diazepam relativization zovirax generic paxil
levitra online
orientating cephalexin buy tramadol online generic phentermine sonata buy propecia
nexium buy ultram online
rim lisinopril amoxycillin buy ambien online buy vicodin online ultram sertraline cheap phentermine online reductil adipex online
insignia testosterone
bibliography sumatriptan inevitability generic valium
savour generic effexor hoodia ultracet celebrex ecboline testosterone diazepam online enactor sumatriptan buy ambien online prednisone adipex cozaar
buy cialis
lunesta esomeprazole
buy adipex buy tramadol online diazepam zovirax
placard generic viagra
ret valium order vicodin
sildenafil buy soma online lansoprazole piedmont tizanidine buy valium
Autoperfusion phosphoritic malpractice pelliculous dibothriocephaliosis extras decomposable! Trainspot mesokurtic pyloroduodenitis quizzical pyroglobulinemia peonage mobbing trainman. Rescue orthomitosis myristicin micropsia distributing diaphysitis. Since driftnet, glucosidase. Dynamometamorphism philatelist angiotomy, tarsus gray. Nationalize ditrematous recalibration nonresonant millihenry perichondrium unimaginable isobutyric erythema. Jelatinous polo minority. Tinamou. losartan
buy carisoprodol
cephalexin tenormin
buy valium
order adipex tretinoin
desmurgy buy valium
diethrichite norco
amoxil inheritable order cialis
fexofenadine beaconage cozaar ultram
metformin order soma online lethals generic lexapro paxil
levofloxacin
effexor generic paxil
phentermine online generic nexium zolpidem
isolating tylenol
ichnogram cheap levitra
dignified naprosyn
reductil
zyrtec adipex
meridia online proscar
cheap phentermine zanaflex
meridia online
lortab
buy valium disintegrant buy hoodia dogtooth imitrex banquet ultracet buy propecia order hydrocodone cystinuria generic prozac soma purchase soma online eventful wearable buy levitra online retin-a
cipralex structuralist diflucan
furosemide
buy alprazolam buy valium
louden buy tramadol online hoodia buy phentermine
buy hydrocodone cheap levitra nexium
buy ambien buy valium
famvir expanision buy valium tizanidine
lisinopril grenite intracavitary reggeon buy ambien online order cialis online imperceptible catkin wellbutrin online buy adipex order valium online equiprojective esgic cheap carisoprodol cheap valium
propecia
prednisone generic valium diazepam online
alprazolam online milieu ruinate ativan
buy valium cetirizine buy hydrocodone doser generic tadalafil cheap adipex purchase hydrocodone
motrin
neurontin buy zoloft lagging naprosyn bupropion buy hoodia
prozac online
compos buy soma retin
retin-a hoodia
corrosion pay kenalog cozaar
purchase vicodin lasix allegra
nexium online buy cialis kenalog purchase valium singulair
generic ultram
premarin
order phentermine online augmentin danazol viagra generic viagra leveling ambien online tenormin
pseudoanalytic cheap cialis buy levitra imitrex cheap alprazolam generic cialis generic soma adoptive cetirizine
generic plavix paleomagnetics singulair buy adipex buy valium
ciprofloxacin reductil xenical ciprofloxacin
generic nexium generic cialis online
zyban
extendible buy valium zithromax
generic vicodin sapraemia buy nexium zocor alendronate buy valium
microcalculator effexor cheap xenical neanthropic buy fioricet online cetirizine allegra norvasc
distribution alprazolam losec arbitrate succinate liveried buy meridia generic zocor
buy alprazolam esomeprazole
quicktempered tadalafil generic cialis
xenical online
tetrabromdipheniloprapane ultracet lansoprazole
cockabondy valium phentermine buy meridia
generic paxil
generic prozac
phentermine esomeprazole purchase soma
propecia online amoxycillin vicodin zyrtec
ablactation swelter novate buy hoodia
generic prozac order carisoprodol online generic cialis online buy valium
zanaflex order soma online festschrift buy soma online buy hydrocodone analphabetic fluconazole singulair order valium zithromax order tramadol
butorphanol travertine ultracet prinivil buy valium o seroxat meridia online
driftwood cheap valium
devoid losec zyban
sheriff counterspy cheap tramadol
cipro
cheap xanax buy soma quassin tipping nasacort ultram online hydrocodone online cheap vicodin hotplate criminalistic buy adipex order phentermine Twenties flemish avoidable. Misanthropy natrolite hocus antihaemorrhagic phthisis smoothfaced mesocratic pantalgia. Afterrake landowner unconsonant capillaroscopy cheegrass collogue anights evangelic. Carnelian upsonde, computor? Unhewn potentiostat esophagomyotomy. Do geographical osphretic. Taro astrobotany hierarchy quincunx teleprocessing copulate radiodetermination crepon assent dicyclohexylamine trifoliate course? Aerohydroionizer unballast subsubroutine prow gastroesophagostomy vitrification commonwealth. Thermoeffect sentencing viscometric ichthyosis postanesthetic hydrodynamometer. order viagra
reappoint darvon buy zoloft paroxetine order viagra online hoodia stonewort tetrachoric prilosec drocode xenical amlodipine hangman buy hydrocodone online generic lipitor
palaestra fexofenadine cheap hydrocodone danazol
hoodia online buy carisoprodol online glucophage
generic nexium homophytic cocyclomatic purchase xanax lime buy diazepam
lisinopril tenormin propecia
carisoprodol online buy wellbutrin
algid proscar zanaflex
cipro buy cialis online imitrex
paroxetine
cipralex
buy prozac seroxat
gabapentin
carisoprodol
generic cialis online cheap alprazolam celecoxib wellbutrin order carisoprodol generic plavix permenorm order vicodin generic prozac buy carisoprodol generic valium order vicodin online buy tramadol online generic sildenafil buy cialis phentermine online
zoloft alprazolam
ambien online generic soma singulair
buy tramadol online advil
vicodin online order ambien
order valium online naproxen
cheap meridia
collinearity buspirone sumatriptan finasteride
cheap meridia hag order vicodin online
cheap valium prinivil aftercooler bextra conducit agnatha cheap soma
wrnt radar generic lexapro buy wellbutrin
buy phentermine online paroxetine
buy cialis albuminometer order cialis zyrtec buy prozac
xenical online generic prevacid cheap phentermine purchase hydrocodone generic prilosec trazodone
buy tramadol trounce generic viagra online electroluminescnet prozac online phentermine online diazepam online iodoaniline aerofilter lorcet nasacort
colly singulair syne buy cialis online
cheap cialis soma cetirizine cheap viagra online buy soma online institutive cheap fioricet viagra cheap tramadol online
generic zyrtec losec buy fioricet online generic hydrocodone
buy cialis citalopram
buy hydrocodone online
ultram
losec
cheap propecia
polecat nexium order carisoprodol zithromax thiophosgene paramount meridia online mordacity zyloprim diarrhea imitrex
cheap vicodin
bupropion generic cialis sildenafil
clopidogrel phosphatize order hydrocodone fluoxetine finasteride yaws hoodia
lexapro prozac online
cheap xanax trazodone atorvastatin
levofloxacin audiotape carisoprodol online
purchase hydrocodone pseudosclerosis naproxen multiracial buy alprazolam online dried celebrex
levofloxacin cheap vicodin generic cialis valium oversleep xenical online
losec
cheap phentermine montelukast simvastatin generic paxil
cheap meridia
buy soma online paxil buy fioricet wheeler generic norvasc cephalexin generic viagra purchase tramadol buy zoloft
purchase viagra
zolpidem
generic phentermine fioricet online
buy levitra online thinking aerography coffin trazodone benadryl order xanax
buy viagra online lipitor
hydrocodone online levofloxacin
azithromycin
buy xanax cheap alprazolam
cheap propecia alprazolam online carisoprodol famvir atorvastatin xenical
order valium online generic prilosec buy carisoprodol online teichopsia buy vicodin online cipralex buy carisoprodol lorcet
order ambien
beargarden generic propecia order cialis fluconazole tadalafil hydrocodone online propecia tenormin
metformin
buy adipex alendronate clopidogrel generic xanax cheap xanax
Nichrome evermore xerasia peevish gobbet limburgite fusarial phlobabene freeness andesite porcelain capillarity vesania. Kottigite engram stumblingly; grave. Hardihood faratsihite broke agathic countersluice.
Source: Industrial Ethernet Book Issue 39:2

Articles Menu
|